How do we calculate the voltage drop?

The calculator works for copper conductors at operating temperature. On a single-phase network it takes the there-and-back path (two conductors), on a three-phase network the factor √3:

ΔU % = k · L · I · cos φ / (γ · A · U) · 100

where L is the one-way length of the cable in metres, I is the current, A is the cross-section in mm², U is the nominal voltage (230 V or 400 V), and k is 2 for single-phase and √3 for three-phase. The resistivity of copper at operating temperature is 0.0225 Ω·mm²/m; its reciprocal is the conductivity (γ).

What does the result show?

  • The voltage drop in percent and in volts.
  • An indication of whether the value is within the selected limit: 3 % for lighting, 5 % for other circuits. A value between the two limits is a "borderline case": acceptable only for a non-lighting circuit.
  • The smallest suitable cross-section from the sizes in the table, for the selected limit.
  • The loss in the cable in watts.

What to watch out for

The calculator takes the cable length as one-way, so do not double it. Leave the power factor (cos φ) at 1 for resistive loads such as heating; enter a smaller value for motors and many kinds of electronics. This calculator does not check the current-carrying capacity of the cable: use the cable cross-section and MCB calculator for that.

Frequently asked questions

How large a voltage drop is allowed?

The calculator offers two limits: 3 % for lighting and 5 % for other circuits; these are the default values of the program's board rules. The actual requirement is set by the designer.

Do I have to enter the cable length there and back?

No. Enter the one-way length in metres; the calculation takes the there-and-back path into account itself.

Does it calculate for aluminium conductors too?

No, the calculator is for copper conductors.