Cable cross-section and MCB calculator
From the power or the current we calculate the operating current and select the MCB and a copper cable of sufficient cross-section, taking the installation method, the temperature and the grouping into account.
Create a drawing Already have an account? Sign in
How does the calculator choose?
First we calculate the operating current from the power (P / (230 · cos φ) for single-phase, P / (√3 · 400 · cos φ) for three-phase), or use the current you entered directly. Then:
- MCB: the smallest standard rating (6, 10, 13, 16, 20, 25, 32, 40, 50, 63 A) that can carry the operating current.
- Cross-section: the smallest copper cross-section whose corrected current-carrying capacity reaches the rated current of the MCB. The capacity depends on the installation method (B2: in conduit or embedded in the wall, C: fixed on the wall), the ambient temperature and the number of circuits running together.
- Voltage drop: if you enter the cable length, the calculator chooses a cross-section for which the drop stays within the selected limit (3 % or 5 %).
What does corrected current-carrying capacity mean?
The base value in the table applies to a 30 °C environment and a single circuit. In a warmer place, or when several circuits run together, the cable can carry less: the temperature and grouping factors take this into account, and both are shown under the result.
Limits of the calculation
It calculates for copper conductors and PVC insulation, on two-core (single-phase) or three-core (three-phase) loaded cables, for installation methods B2 and C. Above 63 A, for aluminium conductors and for other installation methods it gives no suggestion. The result is informative: the selected cable and protection must be approved by the electrical designer.
Frequently asked questions
Why does it not suggest the smallest cable?
Because the cable must also carry the rated current of the MCB, and if you enter the length, the drop must also stay within the selected limit.
What do installation methods B2 and C mean?
B2: multicore cable in conduit or in a building cavity (for example in a chase, embedded in the wall). C: multicore cable fixed directly on the wall, without conduit.
Related pages
- Voltage drop calculator – ΔU on the selected cable
- Power and current converter – the current from the power
- Electrician calculators – all the calculators
In detail in the tutorial
- Distribution boards, single-line diagram and sizing – sizing the protection and the cable in the drawing