Avenler

Power factor correction calculator

Enter the active power and the present and desired cos φ, and we calculate the required capacitor power and the current before and after the correction.

Create a drawing Already have an account? Sign in

How do we calculate power factor correction?

Power factor correction reduces the reactive power with a capacitor, so the apparent power and the current of the load become smaller. The required capacitor power is:

Q = P · (tg φ₁ − tg φ₂)

where P is the active power in kW, and φ₁ and φ₂ are the angles of the present and the desired power factor (you enter the values of cos φ₁ and cos φ₂). The result gives the capacitor power in kvar (kilovolt-ampere reactive).

What else does the result show?

The apparent power (kVA) and the current (A) before and after the correction, on a single-phase (230 V) or three-phase (400 V) network. This shows how much the load on the cables and the protection decreases.

What to watch out for

The target cos φ should be higher than the present one, and at most 1. Size and connect the capacitor according to the manufacturer's data and the designer; the calculator is informative. Take the active power and the present power factor from measurement or from the supplier's bill.

Frequently asked questions

What does kvar mean?

The kvar (kilovolt-ampere reactive) is the unit of reactive power. The power of a capacitor is also given in it.

Does it calculate for single- and three-phase networks too?

Yes. The capacitor power uses the same formula; the network determines the current (230 V or 400 V).

Related pages

In detail in the tutorial

Create a drawing